Error status of the cyclone separator
Displays the current error status of the cyclone separator.
Under-pressure at cyclone separator infeed
Displays the current underpressure upstream of cyclone
separator.
Cyclone separator safety switch
Displays the current status of the safety switch.
Cyclone separator overpressure detected
Indicates whether an overpressure has been detected
upstream of the cyclone separator.
Due to the cyclone separator, the boiler control variable is
limited to
Indicates how much the boiler control variable is limited by
the cyclone separator in percent.
Cyclone separator ID fan controller
Indicates the percentage at which the ID fan of the cyclone
separator is being controlled.
Service
Setpoint under-pressure at cyclone infeed
The cyclone ID fan regulates to this underpressure during
operation.
Minimum pressure in preparation before the cyclone
In “
Preparation
” status, the minimum underpressure
specified must be reached.
Minimum ID fan activation at the cyclone separator
Minimum value at which the cyclone separator can be
activated.
Runtime of the ash screw per heating hour
Indicates the length of time during which the ash can be
discharged to the ash container. The duration is calculated
on the basis of the heating hours of the boiler since the
ash screw was last operational.
Cyclone separator Kp under-pressure monitor
Proportional value of the PI controller of the cyclone ID fan
controller.
Tn cyclone separator under-pressure monitor
Reset time of PI controller of cyclone ID fan controller.
IO allocation
AO ID fan cyclone separator
Indicates the analogue module output at which the ID fan
of the cyclone separator is connected.
AI underpressure transmitter
Indicates the analogue module input at which the
underpressure transmitter of the cyclone separator is
connected.
Setting - Ignition
System menu
System
Setting
Ignition
Feed time until there is a fuel quantity suitable for ignition
Feed time until a sufficient quantity of fuel is present on the
combustion grate to carry out the ignition process.
Duration of pre-heating
Time during which only the ignition is activated. The fuel
slide-in is not active for this duration.
Parameters overview
4
System
Service manual Lambdatronic H 3200 for wood chip boiler | B1480721_en