![Fröling Lambdatronic H 3200 Скачать руководство пользователя страница 86](http://html1.mh-extra.com/html/froling-0/lambdatronic-h-3200/lambdatronic-h-3200_service-manual_2338789086.webp)
4.11.3 Difference regulator - Times
System menu
Diff. control
⇨ See "Setting times" [page 133]
4.11.4 Difference regulator - Service
System menu
Diff. control
Pump output of diff. control pump
Pump outlet to which the pump of the differential controller
is connected.
Control of diff. control pump
Definition of control signal for pump type used.
⇨ See "Activation options of pump outlets" [page 124]
Minimum pump speed
Adjustment of the minimum speed to the pump type (set
mode of pump in accordance with pump manufacturer).
Maximum pump speed
If you need to limit the maximum speed of the pump of the
differential controller for systemic reasons, you can do so
by adjusting this parameter.
Sensor input of heat source sensor
Sensor input to which the heat source sensor is
connected.
Sensor input of heat sink sensor
Sensor input to which the heat sink sensor is connected.
Sensor monitoring
▪ YES: If temperatures around freezing point occur, an
error message appears on the display.
▪ NO: The error messages of the differential controller
sensor are suppressed.
4
Parameters overview
Difference regulator
86
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com