![Fröling Lambdatronic H 3200 Скачать руководство пользователя страница 111](http://html1.mh-extra.com/html/froling-0/lambdatronic-h-3200/lambdatronic-h-3200_service-manual_2338789111.webp)
Minimum output
Minimum value of boiler control variable which can be
used to operate the boiler.
Maximum boost of output to
Maximum opening of the primary air flap at minimum boiler
output.
Start of combustion chamber cooling at cc temp signal
When the combustion chamber temperature signal
reaches the specified value, the combustion chamber
cooling is started.
End of combustion chamber cooling at cc temp signal
When the combustion chamber temperature signal
reaches the specified value, the combustion chamber
cooling stops.
Start of slide-in reduction from cc temp signal
When the combustion chamber temperature signal
reaches the specified value, the fuel slide-in is reduced.
Current cc temp. signal
Display of the current combustion chamber temperature
signal.
CC cooling through secondary air
Display of the current combustion chamber cooling by the
secondary air.
Slide-in is limited to a maximum of
Display of the current feed-in limit during combustion
chamber cooling.
Output boost using combustion chamber control
Display of the current power increase rate due to
combustion chamber regulation.
Parameters overview
4
System
Service manual Lambdatronic H 3200 for wood chip boiler | B1480721_en
111