2.3.3 Setting the module address
The necessary order for hydraulic modules and heating circuit modules is set with the module addresses. The
first board of a module type should always have the address 0, so that the standard hydraulic systems set do
not have to be subsequently configured. For further module types rising module addresses (address 1 - 7) are
set.
Important! Only set the module address when the device is disconnected from the power supply!
Included in standard delivery
Lambdatronic S 3200
Touch control
Address: 0
Heating circuit 1/2
Hydraulic module
Address: 0
Address: 1
Hydraulic module
Heating circuit module
Address: 0
Heating circuit 3/4
Address: 1
RBG Touch 3200
Room console
Core module
Hydraulic module
Hydraulic module
Heating circuit
module
Module
address set
Heating circuit module
Hydraulic module
Heating circuit
Sensors
Pump
0
03 – 04
0.1 – 0.6
0.1 – 0.2
1
05 – 06
1.1 – 1.6
1.1 – 1.2
2
07 – 08
2.1 – 2.6
2.1 – 2.2
3
09 – 10
3.1 – 3.6
3.1 – 3.2
4
11 – 12
4.1 – 4.6
4.1 – 4.2
5
13 – 14
5.1 – 5.6
5.1 – 5.2
6
15 – 16
6.1 – 6.6
6.1 – 6.2
7
17 – 18
7.1 – 7.6
7.1 – 7.2
Power connection and wiring
2
BUS connection
Service manual Lambdatronic H 3200 for wood chip boiler | B1480721_en
35