AUTO
AUTO
Installation and operating instructions profi-air 250/360 flex
60
Automatic mode
Automatic mode
Control unit
Press the button for 5 seconds to control the unit using the automatic mode. The LED
starts flashing to indicate activated automatic mode.
profi-air cockpit app
You can select the automatic mode of operation via the “Programme” menu item.
At least 1 optional sensor (humidity / VOC) must be installed to
control the ventilation unit in automatic mode.
Summer bypass
Automatic summer bypass
The automatic summer bypass is open under the following conditions:
n
The fresh air temperature target value has been exceeded (factory setting: 15 °C).
n
The extract air temperature target value has been exceeded (factory setting: 24 °C).
n
The fresh air temperature is at least 2 °C below the extract air temperature.
The automatic summer bypass closes again if the target values are fallen short off.
Control unit
The LED is lit continuously when the bypass flap is open.
profi-air cockpit app
If the bypass flap is open, the app will no longer show the airflows crosswise.