No. Fault
Possible cause
Remedial action
7 Despite inductive load, no
stages are switched on
when PQC is in automatic
mode.
When the PQC was
programmed, c/k,
switching time delay, or
discharge time have been
set too high.
Check the PQC programming
and change if necessary.
In automatic operation,
the response current
c/k was not correctly
identified.
Check the control circuit
against the connection diagram
and repeat the calibration
procedure.
Another current measuring
instrument (e.g. an
ammeter) has been
connected in parallel with
the current path.
All measuring instruments
in the current path must be
connected in series.
8 In automatic mode, one
stage is continually being
switched in and out
(hunting).
The value of c/k was set
too low when the PQC
was programmed.
Set c/k value correctly
according to the table.
Severe load fluctuations;
the delay time was set too
low.
Set higher delay time.
9 The displayed power
factor (cos
φ
) is less than
the target power factor
although the PQC has
switched in all stages.
Type of connection
incorrectly set.
Reset type of connection.
Fault in control circuit.
Check whether the capacitor
contactors have been activated.
Fault in capacitor circuit.
Check the fuses and contacts
of the capacitor contactors
and possibly also measure
the currents of each capacitor
stage with a tong tester.
System underdimensioned Read off the corrective power
still lacking from the menus.
Faulty calibration
Repeat the calibration
procedure.
10 PQC does not switch out
all stages under low load
conditions or during plant
shutdown.
c/k set too high.
Set c/k according to table.
PQC is in manual mode.
Deactivate manual control.
Wrong control profile
selected
Adjust control profile to suit
requirements.