![frako 38-00400 Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/frako/38-00400/38-00400_operating-manual_2326325011.webp)
11
Alarm contact
Conductor cross section max. 2.5 mm², min. 0.2 mm²
·
Insulation rating: min. 250 V AC, 80 °C
USB for updates
USB Micro-A and Micro-B ports
·
Digital inputs and
PQC version: PQC xxxxxxx-1x:
·
Conductor cross section max. 1.5 mm², min. 0.14 mm²
Insulation rating: 50 V DC, 80 °C
Temperature inputs
PQC version: PQC xxxxxxx-1x:
·
Conductor cross section max. 1.5 mm², min. 0.14 mm²
Insulation rating: min. 50 V DC, 80 °C
Modbus RTU connection
PQC version: PQC xxxxxxx-2x:
·
Conductor cross section max. 1.5 mm², min. 0.14 mm²
Insulation rating: min. 50 V DC, 80 °C
Note:
0.14 mm² = AWG 26; 0.2 mm² ≈ AWG 25;
·
1.4 mm² ≈ AWG 16; 2.5 mm² = AWG 14
Design data
Dimensions (W × H × D)
144 mm × 144 mm × 70 mm casing
·
144 mm × 165 mm × 70 mm including connectors
Mounting
Front of panel in 138 mm × 138 mm cutout to IEC 61554, held
·
by four retaining lugs at the corners of the casing
Maximum screw tightening torque 0.4 Nm
Weight
approx. 770 g without packaging
·
Ingress protection
Front of instrument when mounted in cabinet IP40, when
·
mounted in cabinet with upgrade kit (Item No. 20-50015) IP54;
rear of instrument and terminals IP20; all as per EN 60529
Pollution degree 2 as per EN 61010-1:2011-07
Electrical design
Casing protection class I as per EN 61140
·
Working voltage up to max. 760 V AC absolute value at voltage
measurement inputs.
TNV1 circuits, some of which interconnected:
digital inputs and outputs, optional temperature inputs,
optional Modbus connection.
Casing design
Flammability rating UL 94 V-0 according to casing manufacturer
·
Impact resistance IK06 as per EN 61010-1:2011-07, 8.2.2
Service life
At +25 °C ambient temperature 15 years
·
EMC
EMC as per EN 61326-1
·
EN 61000-4-2, electrostatic discharge: air 8 kV and contact
6 kV with horizontal and vertical coupling plane
EN 61000-4-3, radiated immunity (EMS) 80 MHz – 1 GHz,
horizontal and vertical, level 10 V/m = industrial environment
radiation, Class A
Hardware version V1.0: EN 55022A EMI 30 MHz – 1 GHz =
industrial environment, Class A
From hardware version V1.1: EN 55022A EMI 30 MHz – 1 GHz
= office and residential area, Class B
(service interface)