8.4.1 Stages menu
This menu shows the numbers of the stages (1–12) plus the status (ON/OFF), capacitive power
(determined automatically or set manually) and the number of switching cycles of the selected
stage.
Figure 38 Manual control: Stages menu
Key
Action
Return to Manual
control dialogue
Select stage
Select stage
Switch stage
IN or OUT
–
No.
Stat. (Status)
Q(var)
Switching cycles
No. of the
stage
[1…12]
ON / OFF / [x seconds]
Available stage
corrective power
Number of stage
switching cycles
ON
Switches stage in manually
OFF
Switches stage out manually
[x seconds]
Time remaining until
the capacitor stage can be switched
in again (discharge time)
This is the 3-phase
stage corrective
power.
Figure 39 Example of a selected stage
When a stage is switched out again, this is done immediately. Before this stage can be switched
in again, it is necessary to wait until the capacitor's set discharge time has elapsed. A countdown
of the remaining discharge time is displayed in the Status column. Not until this time has elapsed
can the stage be switched in again. If it is attempted to switch in the stage before the countdown
is finished, the message ‘Not possible’ is displayed
[see Figure 40]
. The stage is then not swit-
ched in automatically after the discharge time has elapsed.