Active power
Reactive power
ind
2
3
cap
Regeneration
Switch in
Switch out
One division =
0.65 × smallest cap.
stage
-3
-2
Key
Action
Profile selection
(Save Yes/No)
Increase
value +
Increase
value -
Back to parameter
selection
–
Target cos
·
φ
0.90 capacitive to 0.80 inductive (in increments of 0.01)
Parallel shift
·
-2.0 to +4.0 (in increments of 0.5)
Limitation
·
-2.0 to +2.0 (in increments of 0.5) and OFF
Switching delay
·
5 to 500 s (in 1 s increments)
Phase
·
L1, L2 or L3: select control phase
Active
·
Activate control profile (only one profile can be active)
Save
·
Save changes in control profile
8.5.2.1 Setting target cos
φ
The desired value of target cos
φ
can be set from 0.80 inductive to 0.90 capacitive in increments
of 0.01.
The mode of operation of this adjustment can be seen in
[Figure 44]
and
[Figure 45]
.
If the system operates within the band range shown, no switching operations will be activated.
However, if the system operates outside the band range, the PQC will try to return to within the
band range with the minimum number of switching cycles.
Figure 44 Control response after setting target cos
φ
= 1, limitation = 0, parallel shift = 0