![frako 38-00400 Скачать руководство пользователя страница 44](http://html1.mh-extra.com/html/frako/38-00400/38-00400_operating-manual_2326325044.webp)
44
Figure 40 Message on failed attempt to switch in a stage
8.5 Settings
The Settings menu is selected from the main menu. It offers the following submenus:
Control profiles
·
5 profiles,
[see Section 8.5.1].
General
·
Capacitor stages, Set limits, Alarm management, Extensions
Factory settings
·
PQC reset, Clear switching cycles
Key
Action
Back to main
menu
Select
Select
Open submenu
–
Figure 41 Settings
8.5.1 Settable control profiles
Five control profiles can be individually selected and edited. The instrument is supplied with the
following factory settings:
Profile
1
2
3
4
5
Target cos
φ
0.92 ind
1.0
1.0
0.92 ind
0.96 cap
Parallel shift
-1.0
0.0
+1.0
-1.0
-1.0
Limitation
+1.0
off
off
off
off
Switching delay
45 sec
45 sec
45 sec
45 sec
45 sec
Phase
L1
L1
L1
L1
L1