4 Mounting the instrument
4.1 Suitable location
[see Section 1.3, Intended use]
The PQC is intended for installation in stationary, weather-protected control cabinets and enclo-
sures located indoors. Exposure to dampness is not permitted. The instrument is installed verti-
cally, usually on the outside of the control cabinet or enclosure, so that the controls and display
are accessible to the operator.
Hardware version V1.0: This is a Class A device. In office and residential areas, it can cause
interference to radio reception. In this case, it may be necessary to take appropriate precautions
with the installation.
4.2 Installing the instrument
Figure 1 PQC dimensions in mm
Upgrade kit for IP54:
In the optional upgrade kit (Article No. 20-50015) a gasket is available that must be used when
mounting the PQC in control cabinets with IP54 ingress protection. It is fitted in the groove at the
rear of the instrument’s front panel (moulded polymer) before the PQC is mounted in the cutout.
The gasket seals the gap between the PQC front panel and the wall of the control cabinet.
7
70
63
37
12
12
168
144
135.5
earthing tab
6.3 mm × 0.8 mm