![frako 38-00400 Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/frako/38-00400/38-00400_operating-manual_2326325063.webp)
63
Settings
General
Capacitor stages
Cyclic switching
ON
Discharge time
60 sec
Fixed stages
0
choke factor (detuning)
7%
Zero stage set limit
80%
Nominal voltage
400 V
Settings
General
Set limits
Switching cycle counters
80 000
THDI
50%
V harmonics
Harmonic
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Set limit in %
2
100
1
6
100
5
0.5
100
0.5
3.5
100
3
0.43
100
0.41
2
100
1.76
I harmonics
100% (all)
Overcurrent ratio
1.2
Voltage blackout (sag) limit
85%
Number of ¼ cycles
2 (½ wave)
Detecting phase
L1
Settings
General
Alarm management
Alarm relay
Alarm
cos
φ
alarm
Undervoltage
Undercurrent
Overcurrent
THDI
Switching cycles
V harmonics
I harmonics
Zero stage (dud) detection
Voltage blackout (sag)
detection
ON/OFF
ON
ON
OFF
ON
OFF
OFF
OFF
OFF
ON
ON