Figure 53 Capacitor stages
Key
Action
Capacitor
stage menu
Change
parameter
Change
parameter
Save
parameter
–
8.5.3.2 Setting alarm limits
The following parameters can be adjusted in the
Set limits
menu:
Switching cycle counter
·
10 k – 500 k (in increments of 1k), default setting 80 k
THDI
·
5% – 500% (in increments of 1%)
V/I harmonics
·
0% – 100% (in increments of 0.01%)
Overcurrent
·
1.00 – 2.00 (in increments of 0.01)
Voltage blackout (sag)
·
50% – 93% (in increments of 1%)
Number of ¼ cycles
·
2 – 4 (in increments of 1)
Detecting phase
·
L1, L2, L3
Key
Action
Back to Settings
Select limit
Select limit
Edit limit
–
Figure 54 Set limits 1/2
Figure 55 Set limits 2/2