48
The set target cos
φ
is therefore the upper limit of the control band. Overcompensation is avoi-
ded.
Figure 47 Control response after setting target cos
φ
= 0.92 ind, limitation = OFF, parallel shift = -1.0
Here the set target cos
φ
constitutes the lower (more inductive) limit of the control band. When
regeneration occurs, the lower (more inductive) limit constitutes a target cos
φ
of 1. This means
that no inductive reactive power can result during feed-in operation.
(This is the recommended setting when operating induction generators in parallel with the
supply network.)
8.5.2.3 Limitation L
This setting gives new possibilities that could not be attained previously due to conflicting requi-
rements.
The range of values for L are -2 to +2 in increments of 0.5, including the setting OFF. Setting L at
1 and the target power factor at 1.00 has the same effect as the parallel shift described above.
If the target cos
φ
is not set at 1, a kink results in the control curve, as shown in the example in
[Figure 48]
. The limitation forms an absolute boundary beyond which the reactive power may not
go.
Reactive power
ind
4
3
cap
Regeneration
Switch in
Switch out
One division =
0.65 × smallest cap.
stage
-2
-1
Active power
Reactive power
ind
2
1
cap
Regeneration
Switch in
Switch out
One division =
0.65 × smallest cap.
stage
-3
Active power
Reactive power
ind
4
3
cap
Regeneration
Switch in
Switch out
One division =
0.65 × smallest cap.
stage
-2
-1
Active power
Reactive power
ind
2
1
cap
Regeneration
Switch in
Switch out
One division =
0.65 × smallest cap.
stage
-3
Active power
Figure 48
Control response after setting
target cos
φ
= 0.92 ind,
limitation = +1.0