SECTION 7
VENT DUCTS AND PIPES
For the air intake/flue gas venting system, specific manufacturer-approved, condensate
acid-resistant pipes and systems must be used, resistant to the etching of condensate
acids.
Flue gas venting pipes are to be installed at an angle towards the boiler so as to allow
condensate to run towards the combustion chamber, which is designed for condensate
collection and drainage.
If this is not possible, condensate collection and drain conveying systems must be
provided condensate stagnation areas.
7.1 100/60 CO-AXIAL AIR/VENT DUCTS
Type of installation: C13 - C33
Maximum pipe length*
TYPE OF
INSTALLATION
PIPE
MATERIAL
KC 24
KR 24
KC 28
KR 28
KC 32
KR 32
Air
intake
Flue gas
vent
Max L [m]
Max L [m] Max L [m]
C13 – C33
aluminium polypropylene
10.0 9.0 7.0
* Excluding the starting curve
Flue fitting load loss
Component
KC 24 – 28 - 32
KR 24 – 28 - 32
[m]
Extension 1m
1.0
Extension 0.5m
0.5
90° elbow
1.0
45° elbow
0.5
Roof vent terminal
1.5
Wall terminal kit + 90° elbow
1.5
IMPORTANT. Minimum length allowed 0.75 metres