________________________________________________________________________________
53
AST 14 C 257/00
Setting the thermoregulation curve
Press the Reset and b oiler status buttons together for three seconds to access the
parameter programming mode.
Use the +/- heating buttons to select parameter P10.
Press OK to confirm that you want to modify the value of the parameter. The spanner
symbol means that you can do this with the +/- heating buttons:
Press OK-info to confirm and press Reset to exit the programming mode.
•
For high-temperature systems, you are advised to set parameter P10 to a value
between 1 and 2.
•
For low-temperature systems, you are advised to set parameter P10 to a value
between 0.2 and 0.8.
Then press OK to confirm the new value and press Reset to exit the programming mode.