AST 14 C 257/00
¾
Flow probe failure
(E05):
the burner switches off immediately and the fan runs at
the ignition power.
The pump runs until the fault is removed, with the diverting valve in the heating
position if before the fault there was a request for heating, flow-return anti-freeze or
chimney-sweep, or there were no request at all.
The pump runs with the diverting valve in the DHW position only if before the fault
there was a request during DHW or anti-freeze operation.
With P17=1 and P17=3 (multifunction relay), the relay remains energised until the
fault is removed if there was a request for heating, flow-return anti-freeze, chimney-
sweep, or there were no request at all.
¾
Return probe failure
(E15):
the burner switches off immediately and the fan runs at
the ignition power.
The pump runs until the fault is removed, with the diverting valve in the heating
position if before the fault there was a request for heating, flow-return anti-freeze or
chimney-sweep, or there were no request at all. The pump runs with the diverting
valve in the DHW position only if before the fault there was a request during DHW
or anti-freeze operation.
With P17=1 and P17=3 (multifunction relay), the relay remains energised until the
fault is removed if there was a request for heating, flow-return anti-freeze, chimney-
sweep, or there were no request at all.
¾
Plate DHW probe failure
(E06)
: when there is a request for operation on DHW
mode, the burner does not activate (it switches off, if it is ON). The pump activates
for as long as the request continues, after which (and without any further requests),
it performs a 30-second post-circulation cycle, which is performed even without any
operation request. When there is a request for operation on heating, flow anti-freeze
or chimney-sweep mode, the request is normally handled.
The system resumes normal operation when the fault is eliminated.
The table below shows the resistance values (Ÿ) of the flow, return, DHW and tank
heater NTC probes at the various temperatures.
Prob e calib ration:
10k Ohm at 25°C
T °C
0
2
4
6
8
0
27203
24979
22959
21122
19451
10
17928
16539
15271
14113
13054
20
12084
11196
10382
9634
8948
30
8317
7736
7202
6709
6254
40
5835
5448
5090
4758
4452
50
4168
3904
3660
3433
3222
60
3026
2844
2674
2516
2369
70
2232
2104
1984
1872
1767
80
1670
1578
1492
1412
1336
90
1266
1199
1137
1079
1023
Correct operating range:
from -20 to +120°C, general tolerance
:
+3°C.