Chapter 2: Certify Twisted Pair Cabling
Set the Reference
37
Make sure that you select the correct cable type for the job,
and that the NVP for the cable is correct. See Table 2 on
page 39.
Make sure you select the correct test limit for the job. See
Table 2 on page 39.
Make sure the cords and connectors for all test equipment
and patch cords are in good condition.
Make sure the battery is fully charged.
Send the modules to a Fluke Networks service center every 12
months for factory calibration.
Set the Reference
The reference procedure for twisted pair cable sets the baseline
for insertion loss, ACR-F, and DC resistance measurements.
Set the reference at these times:
When you want to use the tester with a different module. The
tester can save reference values for eight different pairs of
modules.
When you attach Class F/F
A
link interface adapters, such as the
optional DSX-PLA011 TERA
™
adapters.
Every 30 days, at minimum. To ensure maximum accuracy of
test results, set the reference daily.
It is not necessary to set the reference when you change the link
interface adapters.
To set the reference
1
Turn on the tester and the remote a minimum of 1 minute
before you set the reference.
Note
Set the reference only after the testers are at an
ambient temperature between 50 °F and 104 °F
(10 °C and 40 °C).
Содержание Versiv
Страница 38: ...Versiv Cabling Certification Product Family Users Manual 24...
Страница 86: ...Versiv Cabling Certification Product Family Users Manual 72...
Страница 202: ...Versiv Cabling Certification Product Family Users Manual 188...
Страница 214: ...Versiv Cabling Certification Product Family Users Manual 200...
Страница 234: ...Versiv Cabling Certification Product Family Users Manual 220...
Страница 244: ...Versiv Cabling Certification Product Family Users Manual 230...
Страница 256: ...Versiv Cabling Certification Product Family Users Manual 242...
Страница 258: ...Versiv Cabling Certification Product Family Users Manual 244...