7.3 Type related data of DYNAVERT
®
L05
Short designation
L20 L30 L40 L60
L75
Invertertype
2L
2W-05
400-020
2L 2W-05
400-030
2L 2W-05
400-040
2L 2W-05
400-060
2L 2W-05
400-075
Power supply
Connected load
9)
[kVA]
6,6
8,0
11,7
17
25
Rated current
[A] 9,5
11,5
17
24
36
max. power
), 10)
[kVA]
15 20 24 38
51
max. current
)
[A]
22 29 35 55
74
max. mains fuse
11)
[A]
50 50 50 100
100
Output
Rated power
)
[kVA]
7 10 14 21
26
Rated current
12)
[A]
10 15 20 30
37
max. power
)
[kVA]
14 21 28 45
55,5
max. current
13)
[A]
20 30 40 60
75
Brake resistor
Constant power S1
14)
[kW]
0,7 1,9 1,9 3,0
4,0
Stationary power
15)
[kW]
2,6 7,0 7,0 10,5
14,5
Mechanical data
Dimensions
H x B x T
16)
[mm] 700x 254x310
700x 254x310
700x 254x310
1000x254x310 1000x254x310
Weight
[kg]
25 25 25 36
36
Clearance cooling air
17
on top
below
[mm]
[mm]
250
150
250
150
250
150
250
150
250
150
Dimension sheet No.
125
125
125
126
126
Connection mains
18)
10
mm
2
10
mm
2
10
mm
2
25
mm
2
/ M6
25 mm
2
/ M6
Connection motor
Fehler!
Textmarke nicht definiert.
)
[mm
2
] 6
10
10
16
16
Required cooling air
19)
[m
3
/h]
150 260 260 260
280
Dissipation
20)
[kW] 0,14 – 0,84
0,17 – 2,07
0,25 – 2,15
0,4 – 3,4
0,5 – 4,5
9)
Output data apply to the voltage rating of the device (400 V).
10)
Short-time performance: does not occur on lift installations owing to the typical torque characteristic.
11)
Maximum admissible rated fuse-value; normale line protection fuses, classification "gL" or "gG" acc.to DIN/VDE 0636.
12)
Thermal equivalent permanent current for S1-operation (= thermal capacity DYNAVERT L). This value can be monitored by means
of the thermal model for the respective inverter; monitoring-limits adjustable. Anouncement by pre-warning signal. The stationary
motor current may reach up to 150% of the rated current for a period of 60s. ON-period 60s.
13)
The output current is limited to these values.
14)
Mean continuous power for typical lift operation.
15)
For contant travel with generative operation of max. 30s.
16)
Measures without additional appliances like crane-eyelets, fixing angles etc. (exact data: see dimension sheets).
17)
Required clearance for the inlet and outlet air of the device (min. distance on top and below);
Caution:
The outlet temperature on top can amount up to 150 °C.
18)
Maximum connectable cross section at the terminals resp. size of the terminal stud in case of screw terminals.
19)
In case of wall mounting ensured by observing
clearance cooling air
. If special inlet and outlet air-ducts are used for the device,
these must be dimensioned for the indicated cooling air flow rate.
20)
The lower value means the max.dissipation of the inverter, the higher one the total loss incl. the max. possible energy recovery.