Troubleshooting instructions
4BS0516DE-EN/011
Stand/ issue: 25.07.03
41
5.4.1.3 General
faults
Faults,
displaying
"!! Fault!!
" in the first line, can be acknowledged by means of an inverter
reset
(
and
-
RESET
)
, provided the cause of the fault is no longer existing.
These are faults, causes of which are not necessarily due to a defective inverter.
They could as well be caused by wrong settings (parameterising) or by external influences.
In case of the faults mentioned below the
inverter is switched of electronically,
the failiure
must
be
acknowledged
always
with “
inverter reset
” :
Message
on the display
Event memory
Probable cause of the fault
!! Fault !!
Overvoltage
Flt>Overvoltage
Line voltage too high; extreme generative operation; wrong or no brake resistance;
wrong setting of parameter
P-INVERTER DATA: V mains nom.
.
!! Fault !!
Undervoltage
Flt>Undervoltage
Line voltage fault or genuine undervoltage; fuse defective, wrong setting of parameter
P-INVERTER DATA : V mains nom.
.
!! Fault !!
Fail. mains phase
Flt>Fail.mains ph.
Line voltage fault; phase fault; mains fuse defective
!! Fault !!
SC phase U
Flt>Short Ph.U
Short circuit in inverter-phase U, in cable inverter output to motor or in the motor
!! Fault !!
SC phase V
Flt>Short Ph.V
Short circuit in inverter-phase V, in cable inverter output to motor or in the motor
!! Fault !!
SC phase W
Flt>Short Ph.W
Short circuit in inverter-phase W, in cable inverter output to motor or in the motor
!! Fault !!
Earth fault
Flt>Earth fault
Fault in the motor or in the motor cable; device-internal earth leakage; motor cable too
long; insufficient insulation resistance
!! Fault !!
Fault Tacho
Flt>Fault Tacho
Fault of the connected sensor resp. of sensor cable (sensor supplies unplausible
values)
!! Fault !!
Direction Signal
Flt>DirectionSig.
No directional information to the DYNAVERT
®
L05 or both direction inputs
(
X1:36
;
X1:37
) low resp. high unpermitted condition; parameterising for direction
default is faulty (see
P-SYSTEM DATA: Dir-Sign
)
!! Fault!!
Travel Contactor
Flt>Travel Cont.
Travelling contactor does not drop after completion of trip; connection
X1:28
to
X1:38
via breaker of the installed travel contactors is missing
!! Fault !!
current flow
Flt>Current flow
Current flow despite deactivated travelling contactor
!! Fault !!
ContrRelease not off
Flt>ContRel.n.off
Controller released despite deactivated travelling contactor