DYNAVERT
®
L05
Commissioning instr
4BS0516DE-EN/011
Stand/ issue: 25.07.03
27
2. Menü:
P-TRAVEL CURVE DATA
Setting of the commissioning parameters:
v 3, v Posi, BrkDis v3, StopDist, Position
v 3
v Posi
StopDist
Position
BrkDis v3
Fig. 13: Example: Braking distances and designation of travelling curves:
Process of the position control / Autom. start of deceleration
- Upon setting of the parameters the inverter carries out plausibility checks.
- Faulty or incorrect settings will be commented in the display and must be corrected!
For the setting of the travelling distances in
P-TRAVEL CURVE DATA
the following tabular values are to be observed.
v3
(m/s)
v Posi
(m/s)
BrkDis v3
(cm)
StopDist
(cm)
Position
(cm)
up to 0,8
0,05
more than 125
8
10
0,8...1,6
0,1 125...315 12
12
1,6... 2,5
0,15 315...600 18
25
Stoppage points in the shaft or
digital shaft information
Maximum acceleration and deceleration depend always on the selected travelling speed, as shown
in the diagram.
V
(m/s)
Positioning
distance
Stopping
distance
Automatical deceleration.
Initiation by inverter
Levelling
t (s)
Stop switch
Default by lift control (shaft switches
or digital shaft information)
Braking vane
Default by lift control (shaft switches
or digital shaft information)
Braking distance