Troubleshooting
instructions
DYNAVERT
®
L05
46
Stand/ issue: 25.07.03
4BS0516DE-EN/011
5.4.4 General messages on the display
In addition to the fault signals the inverter writes out general messages in the status display.
These messages give instructions for operation and parameterising of the inverter.
Fault message
on the display
Cause of the message
Initialization
in process
The inverter is getting initialized after line voltage is “ON” or of “Processor-Reset”.
Sensor adjustm.
in process
Presently, an “automatic” sensor adjustment is made.
Controller release
missing
A travelling command has been set but controller release is missing.
not possible !
Sensor adjustment not possible at the time being (e.g. owing to fault) or controller
release (+24V an
X2:3
) missing.
Para. protected !
With the actual setting of
S1.1
no parameter can be changed.
Remedy: Set dip-switch
S1.1
(see fig. 5) to “
On
”
no inverter off !
The inverter shall not be operated while the selected parameter is changed.
Write error RTC
Error upon writing of the RTC (clock module)
Write error EEPROM
Error upon parameterising (writing of the EEPROM).