Commissioning
instr
DYNAVERT
®
L05
26
Stand/ issue: 25.07.03
4BS0516DE-EN/011
4.3 Commissioning with positioning travel
(Activation via terminals or DCP-interface)
4.3.1 Parameterising
1. Menu:
P-OPERATION
Setting of the actual LCD-display language:
Language
Generally, the frequency inverter is supplied bilingual, i.e. at present in
German
and
English
(factory setting is
German
).
Besides of parameter
Language
change-over to the other language (e.g. the national language)
can also be carried out by means of the “status”- key (no saving).
For that, the
- key must be pressed for about 3 seconds; change-over to the other language is
made automatically.
Setting of the required application:
A
Following
applications
can be parameterised:
- Lift with asynchronous drive and HTL-encoder 1024
->
asynchron HTL1024
- Lift with synchronous drive (SAD-motor, encoder ERN1387) ->
synch.SAD ERN1387
- Lift with asynchronous drive and HTL-encoder 1024, and
DCP-interface
->
asynchron DCP Res
- Lift with synchronous drive (SAD- motor, encoder ERN1387
and DCP-interface)
->
synch.SAD DCP Res
- Set of parameters was changed manually
->
specific
- Always that application must be set, which meets exactly the actually
existing configuration!
- If this is not possible as, for example, an encoder with another resolution is used,
application A
must be adjusted so, that it comes closest to the actually existing
configuration.
Example:
- Application:
“ Lift with asynchronous drive and HTL-encoder
with 2048 pulses/revolution “
Setting of application:
A
to
asynchron HTL1024
Setting of menu :
Menu
to
Standard
Check of parameters
P-MOTOR DATA : encoder
to
HTL-encoder
Setting of parameters
P-MOTOR DATA : Pulses/360
to
2048
Reset of menu:
Menu
to
Commissioning