Commissioning
instr
DYNAVERT
®
L05
28
Stand/ issue: 25.07.03
4BS0516DE-EN/011
Setting of
Accel.
and
Decel.
in menu
P-TRAVEL CURVE DATA
to be made as
per values given in
Table 1
!
Recommended setting values for closed-loop controlled lifts
Setting of commissioning parameters
Accel.
and
Decel.,
following the acceleration limit values listed
below:
Rated speed parameter
v3
Acceleration parameter
Accel.
Deceleration parameter
Decel.
up to 0,5 m/s
0,5
m/s
2
more than 0,5m/s up to 1,0m/s
0,7
m/s
2
more than 1,0m/s up to 1,6m/s
0,8
m/s
2
more than 1,6m/s up to 2,0m/s
0,9
m/s
2
more than 2,0m/s up to 2,5 m/s
1,0
m/s
2
Table 1: Acceleration/Deceleration values
Recommendations for the setting of the braking distance:
- Read out/take down information menu parameter
I-MIN.BRAKE.DIST.: BrkDis3
.
- As reference value for the required braking distance multiply this factor with 1.05
and mount the braking vane accordingly.
- The actual distance of the vane from the level position is now set in menu
P-TRAVEL CURVE DATA
, parameter
BrkDis3
.
Acceleration limiting values
0,00
0,20
0,40
0,60
0,80
1,00
1,20
0,5
1
1,5
2
2,5
rated speed v3 (m/s)
Accel. / Deceleratio (m/s2)
Passenger lifts
Good lifts