DYNAVERT
®
L05
Commissioning instr
4BS0516DE-EN/011
Stand/ issue: 25.07.03
31
Generally applies:
A reduction of amplification would cause an increased “stalling“ of the car upon
starting. If the values are too high, a short generation of noise in the motor will
occur in most cases during the starting phase.
Setting of parameter
Gear losses
.
If problems arise upon starting (e.g. owing to friction torques in the lift system),
an appropriate evaluation can be carried out with this parameter:
higher value in case of higher friction torques in the lift system
lower value with roller guides and high gear efficiency
6.
Menu: P-MOTOR DATA
Set motor data taken from type plate:
-
n-Motor
(rated-rpm)
-
I-Motor
(current)
-
f-motor
(frequency)
-
V-motor
(voltage)
-
cos phi
(cos phi)
(
required only for applications with asynchronous motor)
7.
Menu: P-INVERTER DATA
Setting of the actual mains voltage in parameter
V mains nom..
8.
Menu: P-INTERFACE
Set parameter
Op.-source
and
RS485 Prot
.
For activation over terminal or DCP-Interface apply to settings:
Terminal
DCP
Op.-source
Termin.
RS485
RS485
Prot - DCP