eCO Premium™ - Installation & Maintenance
35
FläktGroup DC_9604GB_20190327_R6
Specifications are subject to alteration without notice
15. MINIMUM SPACE REQUIRED FOR THE MAINTENANCE
16. CONDENSATION REMOVAL AND DRAIN TRAP
MINIMUM MAINTENANCE SPACE, CONDENSATION REMOVAL AND DRAIN TRAP
Maintenance side
0.6 x Width Minimum
0.5 x Width Minimum
Services side
Unit Size
Unit Width
(mm)
1
1220
2
1220
3
1520
4
1520
5
1720
6
1720
The unit is equipped with a condensate drainage point to which a
drain trap should be attached, to ensure effective evacuation
of water during normal operation. Any drain trap should be as
detailed below and should have a minimum slope of 3°.
Use of a drain trap is essential for the proper functioning of the
energy recovery unit, in order to prevent air being sucked in and
also to promote the natural flow of condensate. A drain trap is
available as an accessory.
DIMENSIONS
Pa
H
L
Under pressure
Pa
Cut to size
(L)
Height
(H)
< 600
50 mm
40 mm
600-1000
70 mm
60 mm
1000-1400
110 mm
100 mm
1400-1800
150 mm
140 mm
1800-2200
190 mm
180 mm
2200-2600
200 mm
220 mm