eCO Premium™ - Installation & Maintenance
31
FläktGroup DC_9604GB_20190327_R6
Specifications are subject to alteration without notice
PARAMETER LIST, CONT.
1)
R/W = Read and write value, R = Read only value
Parameter
Type of value
1)
Range
Unit
Default value
Comments
Set Date and Time
R/W
–
–
–
Set Language
R/W
–
–
Swedish
Login
R/W
0000-9999
–
0000
For installers and Service personnel
Settings
For installers and Service personnel
1. Schedule
See page 21.
2. Commissioning Wizard
See page 20.
3. Timer Control
See page 21.
Timer control
R/W
1-6
–
4
Timer Release Delay
R/W
0-9999
min
0
4. Fan Control
4.1 Fan Settings
Boost Running Timer
R/W
Yes / No
–
No
Boost Running Time
R/W
0-9999
min
120
Startup Time
R/W
0-32767
s
15
Extract Fan starts directly,
Supply Fan after selected time
Shut Down Time
R/W
0-32767
s
0
180 sec for unit with Electrical heater
4.2 COP / CAV
Constant pressure / Constant air volume.
For units ordered with Pressure sensors
Pressure Control Supply air
R/W
Yes/No
Yes
Pressure Control Extract air
R/W
Yes/No
Yes
Airflow Control Supply
R/W
Yes/No
Yes
Airflow Control Extract
R/W
Yes/No
Yes
Only Supply, Extract as slave
R/W
Yes/No
No
Ratio Supply/Extract
R/W
0-200
%
100
Supply air pressure Set point
R/W
0-2000
Pa
150
Extract air pressure Set point
R/W
0-2000
Pa
150
Supply, Trickle Airflow Set point
R/W
0-9999
l/s
-
Supply, Normal Airflow Set point
R/W
0-9999
l/s
-
Supply, Boost Airflow Set point
R/W
0-9999
l/s
-
Extract, Trickle Airflow Set point
R/W
0-9999
l/s
-
Extract, Normal Airflow Set point
R/W
0-9999
l/s
-
Extract, Boost Airflow Set point
R/W
0-9999
l/s
-
5. Heating / Cooling
5.1 Pre Heater
Pre Heater (accessory, stand alone)
not connected to ERU
Pre Heater
R/W
Yes/No
-
No
Warming Filter
R/W
Yes/No
-
No
5.2 Heating/Cooling
See page 24.
Control mode
R/W
1-2
1
1 = Standard, supply air control
2 = Cascade control
Minimum Supply temp
R/W
15-35
°C
15
Maximum Supply temp
R/W
15-35
°C
25
Cooling
R/W
Yes/No
No
Cooling DX
R/W
Yes/No
No
Dead zone Cooling
R/W
Yes/No
Yes
Dead zone
R/W
0-25
°C
2
Block cooling in Winter
R/W
Yes/No
Yes
Block heating in Summer
R/W
Yes/No
Yes
Post Heater
R/W
On/Off
On
Cascade reference
R/W
0-1
0
0 = Extract air control
1 = Outdoor air compensation
Cascade A
R/W
–10-10
°C
0,5
Cascade B
R/W
–10-10
°C
–0,5
Relative absolute temperature
R/W
rel/abs
abs
Relative or absolute temperatures in Schedule
SETTINGS