eCO Premium™ - Installation & Maintenance
10
FläktGroup DC_9604GB_20190327_R6
Specifications are subject to alteration without notice
Control Board
Pressure Sensor
Supply air
(Optional)
Pressure Sensor
Exhaust air
(Optional)
Temperature Sensor
Supply air
Temperature Sensor
Freeze protection
(Standard with Hot Water Coil)
Temperature Sensor
Outdoor air
Temperature Sensor
Extract air
Temperature Sensor
Defrost
Control signal
Exhaust fan
Control signal
Supply fan
Filter monitor
Supply
(Optional)
Modbus RS485
Filter Monitor
Extract
(Optional)
Not for size 6 with electrical post heater
230V, 1
~ 50Hz
400V, 3
~ 50Hz
Size 6 with electrical post heater
Electrical guide for supply and internal fuses
Electrical Pre Heater has separate power supply
Fuse F2 only with electrical Post Heater
External Safety Switch
(Accessory)
* Recommended Fuse for units with Electrical
Heater, for units without Electrical Heater 1x10A
Power supply
Size Supply*
F1
F2
1
1x10A
1x10A
—
2
1x10A
1x10A
—
3
1x16A
1x10A
1x10A
4
1x16A
1x10A
1x10A
5
1x16A
1x10A
1x16A
6
3x10A
1x10A
2x10A
(Only units with electrical post-heater)
Power supply electrical post-heater
Size 3-5
Size 1-2
Supply fan
Exhaust fan
Size 6
WIRING DIAGRAM