PARAMETER LIST, CONT.
1)
R/W = Read and write value, R = Read only value
Parameter
Type of value
1)
Range
Unit
Default value
Comments
7.2 Alarm categories, cont.
Filter Alarm Supply
R/W
A/B
–
B
Filter Alarm Extract
R/W
A/B
–
B
Electrical Heater Error
R/W
A/B
–
A
Pump Heater Malfunction
R/W
A/B
–
A
Frost Protection
R/W
A/B
–
A
Alarm Cooling
R/W
A/B
–
B
Pump Cooling Malfunction
R/W
A/B
–
B
Temperature alarm
R/W
A/B
–
A
RHE Belt Alarm
R/W
A/B
–
B
Not for eCO Premium
7.3 Alarm Delays
Fire Alarm
R/W
0-9999
s
2
External function
Sensor Error Supply
R/W
0-9999
s
5
Sensor Error Outdoor
R/W
0-9999
s
5
Sensor Error Extract / Room
R/W
0-9999
s
5
Sensor Error Frost Protection
R/W
0-9999
s
5
For unit with Hot Water Coil
Sensor Error Defrost
R/W
0-9999
s
5
Sensor Error AI10
R/W
0-9999
s
5
Not for eCO Premium
Supply Fan Error
R/W
0-9999
s
60
Extract Fan Error
R/W
0-9999
s
60
RHE Failure
R/W
0-9999
s
5
Not for eCO Premium
Filter Alarm Supply
R/W
0-9999
s
60
Filter Alarm Extract
R/W
0-9999
s
60
Electrical Heater Error
R/W
0-9999
s
2
Pump Heater Malfunction
R/W
0-9999
s
2
Frost Protection
R/W
0-9999
s
2
Alarm Cooling
R/W
0-9999
s
2
Pump Cooling Malfunction
R/W
0-9999
s
2
Temperature alarm
R/W
0-9999
min
10
RHE Belt Alarm
R/W
0-9999
s
120
Not for eCO Premium
7.4 Contact functions NO/NC
DI1 Timer 1
R/W
NO/NC
–
NO
DI2 Timer 2
R/W
NO/NC
–
NO
DI3 RHE Rotation Guard
R/W
NO/NC
–
NO
Not for eCO Premium
DI4 Defrost pressure switch
R/W
NO/NC
–
NO
Not for eCO Premium
DI5 Filter Alarm Supply
R/W
NO/NC
–
NO
DI6 Filter Alarm Extract
R/W
NO/NC
–
NO
DI8 Fire Alarm
R/W
NO/NC
–
NC
DI9 Cooker Hood
R/W
NO/NC
–
NO
Not for eCO Premium
DI7 Alarm Heater
R/W
NO/NC
–
NO
NC with Electrical Heater
DI10 Alarm cooling
R/W
NO/NC
–
NO
8. Configure
8.1 IP Address
Static / Dynamic
R/W
Static/Dynamic
Static = Manual
Dynamic = Automatic via DHCP
IP Address
R/W
–
–
–
Subnet Mask
R/W
–
–
–
8.2 Menu Configure
Log to USB
R/W
Yes/No
–
No
For Service Personnel
Unit Type
L
–
–
Ecostar
Also for eCO Premium
Auto logout time
R/W
0-32767
min
10
Threshold Heater
R/W
0-100
%
0
For Service Personnel
Threshold Cooling
R/W
0-100
%
0
For Service Personnel
Threshold Heat Exchanger
R/W
0-100
%
0
For Service Personnel
Threshold External Fan
R/W
0-100
%
5
For Service Personnel