eCO Premium™ - Installation & Maintenance
30
FläktGroup DC_9604GB_20190327_R6
Specifications are subject to alteration without notice
PARAMETER LIST
Some parameters and functions have a more detailed explanation after the parameter list. The ISYteq Touch 3.5 control panel has a wide
range of applications. Only relevant parameters are listed below. It is strongly recommended to avoid the adjustment of any system
parameters that are not outlined in this section.
1)
R/W = Read and write value, R = Read only value
TEMPERATURE STATUS
Parameter
Type of value
1)
Range
Unit
Default value
Comments
Supply air sensor
R
–40-100
°C
–
Outdoor air sensor
R
–40-100
°C
–
Extract/Room air sensor
R
–40-100
°C
–
Frost protection sensor
R
–40-100
°C
–
For unit with Hot Water Coil
Defrost sensor
R
–40-100
°C
–
Set point
R/W
15-35
°C
19
Summer / Winter mode
R
Summer / Winter
–
–
Output signal, Post Heater
R
0-100
%
–
Output signal, Pre Heater
R
0-100
%
–
Not for eCO Premium
Output signal, Heat Recovery
R
0-100
%
–
Not for eCO Premium
Output signal, Cooling
R
0-100
%
–
Control mode / Calculated Set point
R
15-35
°C
–
FAN STATUS
Parameter
Type of value
1)
Range
Unit
Default value
Comments
Supply Fan, speed
R
0 or 30-100
%
–
Extract Fan, speed
R
0 or 30-100
%
–
Pressure Supply air
R
0-2000
Pa
–
For unit with COP
Pressure Extract air
R
0-2000
Pa
–
For unit with COP
Suppy air pressure set point
R
0-2000
Pa
–
For unit with COP
Extract air pressure set point
R
0-2000
Pa
–
For unit with COP
Air flow, Supply air
R
0-9999
l/s
–
For unit with CAV
Air flow, Extract air
R
0-9999
l/s
–
For unit with CAV
Supply air flow, Set point
R
0-9999
l/s
–
For unit with CAV
Extract air flow, Set point
R
0-9999
l/s
–
For unit with CAV
AIR QUALITY
Parameter
Type of value
1)
Range
Unit
Default value
Comments
CO
2
value
R
0-2000
ppm
–
In extract air
CO
2
, Set point
R
0-2000
ppm
800
SYSTEM OVERWIEV
Parameter
Type of value
1)
Range
Unit
Default value
Comments
Software version, Control panel
R
–
–
–
Bootloader version, Control panel
R
–
–
–
Software version, Control board
R
–
–
–
Bootloader version, Control board
R
–
–
–
Unit type
R
–
–
Ecostar
Also for eCO Premium
IP Octet 1
R
0-255
–
–
IP–address, accessory
IP Octet 2
R
0-255
–
–
IP Octet 3
R
0-255
–
–
IP Octet 4
R
0-255
–
–
SCHEDULES
Parameter
Type of value
1)
Range
Unit
Default value
Comments
Schedule
R
–
–
–
Active schedules only, read only