eCO Premium™ - Installation & Maintenance
45
FläktGroup DC_9604GB_20190327_R6
Specifications are subject to alteration without notice
26. TROUBLE SHOOTING (GENERAL)
Fault
Possible Cause
Suggested Action
Unit is difficult to start
Reduced supply voltage
Ensure voltage is consistent with motor name plate data
Insufficient air capacity
Clogged ductwork and/or extract points Clean ductwork and suction point
Insufficient pressure
Clogged impeller
Clean impeller
Dirty filter
Clean or replace filter media. Note: always use original media
type to guarantee unit performance.
Insufficient rotation speed
Check Supply Voltage and if necessary, correct.
Clogged heat exchanger
Clean heat exchanger block
Airflow Performance
drops after a period of
acceptable operation.
(See above)
Air leak before and/or after the fan
Damaged impeller
Check connections and unit casing and restore to original
“as installed” condition.
Check impeller. If necessary, replace with an original spare part
Heat Exchanger Discharge
air temperature too low
External air lower than –5° C
Employ a post heating device
Insufficient Heat
Exchanger performance
Build up of dirt on Heat Exchange fins
Clean Heat exchanger
Frost formation on
External air inferior to -5°C
Employ a pre heating device (frost protection heater)
Heat Exchanger
Airflow hunting
Clogged or wrong ductwork connection
Modify the ductwork and/or replace fan.
Clean and/or replace the suction duct
TROUBLE SHOOTING