18
BASIC SET UP PROCEDURE/LED INDICATION
TASK
ACTIONS
LED STATUS
Flame
Strength
(8)
Ready
Flame
On/Off
Learn
Target
Flame
Learn
Background
Flame
RUN
(none)
All Active
ON
Active
OFF
OFF
Enter
Password
Simultaneously depress:
Target Flame Select
and
Background Flame Select
buttons, then release
Disabled
ON
Active
ON
ON
Depress and release:
UP
button five times
5th ON
ON
Active
ON
ON
Accept
Password
Simultaneously depress:
Target Flame Select
and
Background Flame Select
buttons, then release
5th ON
FLASH
Active
FLASH
FLASH
Aim
Scanner
Depress and hold*:
Target Flame Select
button
Adjust scanner alignment for
flame maximum signal then
secure scanner position.
All Active
FLASH
ON
*(RF is energized if
Target Flame Select
button is held)
ON
OFF
Learn
Target
Flame
Depress and release:
UP or DOWN
button while
holding
Target Flame Select
button*
All Active
FLASH
ON
*(RF is energized if
Target Flame Select
button is held)
FLASH
OFF
Learn Target Flame completed
All Active
ON
Active
OFF
OFF
Learn
Background
Flame
(if required)
Enter and Accept Password as
described above
5th ON
FLASH
Active
FLASH
FLASH
Depress and release:
Background Flame Select
button
All Active
FLASH
Active
OFF
ON
Learn Background Flame
completed
All Active
ON
Active
OFF
OFF
RUN
(none)
All Active
ON
Active
OFF
OFF
*WARNING: Depressing and holding the “Target Flame Select” button during the AIM
and Learn Target Flame procedures will keep the flame relay contacts closed, allowing the
burner to operate without bypassing the burner management system input.
During this process you must visually confirm that the flame is present.
Only when the “Target Flame Select” button is released will the flame relay status be
determined by the actual flame signal strength