21
®
ADVANCED PROGRAMMING AND OPERATION
Reset to a Default File/Profile
Step 1 - Enter the pass code
Press both the
Target Flame Select
and
Background Flame Select
buttons simultaneously.
Use the
UP
or
DOWN
buttons to select LED number
[6]
(passcode).
Press both the
Target Flame Select
and
Background Flame Select
buttons simultaneously.
LED indication at this point:
Ready = ON
Flame On/Off = OFF
Target Flame Learn = ON
Background Flame Learn = ON
Signal Strength LEDs = Flashing
PASS CODE ACCEPTED
Step 2 - Commit the Default File/Profile to EEPROM
To save the Default Profile to the scanner's permanent memory and exit this mode: Press and hold the
Background Flame Select
button for at least 2 seconds.
To
exit
this mode without
saving
: Press the
Target Flame Select
and
Background Flame Select
buttons
simultaneously
.
READY FLAME
= OFF
= ON
= FLASHING
CAUTION: To ensure safe and reliable detection it is the responsibility of the commissioning
Ensure that the scanner correctly detects the target flame (Flame On condition) and
engineer to carry out flame failure testing after programming the scanner.
recognizes the target flame off (Flame Off condition).