11
®
8.
Once the target flame has been learned/stored at the lowest acceptable setting for flame on con-
dition (not less than 3 to 4 LED's on the scanner), the 4 to 20mA output is automatically ranged
to give 4mA at that learned setting (4 LED's) up to 20mA at maximum (8 LEDs). Below 4
LED's the signal will remain at minimum or 4mA.
FIGURE 7.
59-546-X CABLE CONNECTOR 8 PIN LOCATION
Table 4:
SCANNER CABLE COLOR CODE
NEW 59-546 CABLE COLOR CODE
(Connector Pin No.)
FUNCTION
OLD 59-497 CABLE COLOR CODE
For reference only
(2) Black
24 vdc Input (+)
Black / Red
(6) Blue
24 vdc Input (-)
White / Blue
(8) Yellow
Flame Relay Contact (n.o.)
White / Red
(5) Orange
Flame Relay Contact (n.o.)
White / Black
(7) Brown
Fault Relay Contact (n.c.)
Red
(3) Tan
Fault Relay Contact (n.c.)
Pink
(4) Violet
4-20 ma Analog Output (+)
Violet
(1) Red
4-20 ma Analog Output (-)
Grey / Red
Shield Drain Wire
Earth Ground
Shield Drain Wire
8 CONDUCTOR CABLE
FEMALE END VIEW
(VIOLET)
(YELLOW)
(BLUE)
(ORANGE)
(BLACK)
(RED)
2
SHIELD
5
7
6
8
3
4
1
(TAN)
(BROWN)