Note: There is a time limit function associated with manual use of the flame relay output. If this time
period of two minutes is exceeded, repeat from step one.

AIM MODE

Aim mode sets the scanner to maximum gain.

Keeping the target flame button depressed, use the flame strength LEDs to adjust the scanner “aim” to get
maximum signal (1 LED is the lowest, 8 LEDs are the highest). Look for 3 to 4 LEDs as a minimum.

LED indication at this point:

Ready = Flashing

Flame On/Off LED = ON

Flame Learn LED = ON

Background Learn LED = OFF

Flame Strength LED = Flame Signal

Press either the UP or DOWN pushbutton once to learn the selected flame.

LEARN MODE

Learn Mode initially sets the scanner to minimum gains and adjusts it up to the correct level.

The Flame Strength should BRIEFLY GO BELOW 6 LEDs. If the LEDs stay at 7 or above, add orifices
to minimize the signal (see page 28). If the signal strength does not drop below 6 LEDs, then decrease the
size of the orifice. This may require some testing to determine the correct size.

Note: The “Ready” and “Target Flame” LEDs flash during the learn or store process until it has
been completed.

WARNING: Flame must be present during scanner setup. Verify flame condition prior to
depressing the Target Flame select button and energizing the flame relay output. During
the setup process, run the flame at the lowest acceptable setting for flame on condition, e.g.
low fire or pilot if the scanner is required to detect the condition. The scanner is at maxi-
mum gain during this mode.

READY FLAME

= OFF

= ON

= FLASHING

READY FLAME

FLAME 
STRENGTH

 

TARGET

= OFF

= ON

= FLASHING

Содержание 85IRF series

Страница 1: ...K3 Flame Scanners are derivatives of the standard Phoenix product but utilizing an advanced optical filter This filter adjusts the optical sensitivity of the detection cell to pick up wavelengths of l...

Страница 2: ...UNTING FLANGE P N 35 318 1 2 ORDERED SEPARATELY DIMENSIONS IN INCHES MM PURGE AIR CONNECTION 3 8 18 NPT OR 3 8 19 BSP PL 1 11 1 2 NPT OR 1 11 BSP PL SIGHT PIPE CONNECTION 1 46 36 97 1 84 46 79 HOUSING...

Страница 3: ...X X 85IRF1 2QD X X X X X X X X X X X 85UVF1 2QD X X X X X X X X X X X 85UVF1 1QDK3 X X X X X X X X X X 85UVF1 2QDK3 X X X X X X X X X X X CERTIFICATION IN HAND Table 2 PART NUMBER DESCRIPTION NOTES 35...

Страница 4: ...NUMBER DESCRIPTION LENGTH METERS FEET 59 546 3 8 Conductor 3 meter cable assembly with 8 pin female connector 3 meters 9 feet 10 inches 59 546 6 8 Conductor 6 meter cable assembly with 8 pin female c...

Страница 5: ...and or use with dirty dusty fuels may require up to 15 SCFM 425 l min Pressure Adequate to overcome furnace or windbox pressure ELECTRICAL Input Power 24 Vdc nominal 20 15 supply current 200 mA Elect...

Страница 6: ...me reliably thus prohibiting the delivery of fuel to the burner Note Ensure the correct FFRT Flame Failure Response TIme is selected prior to commissioning INSTALLATION PROCEDURE 1 The best results ar...

Страница 7: ...and close to the periphery of the throat where the ultraviolet radiation is at a maximum See Figures 3 and 4 Having determined an appropriate location for the sight tube cut a clearance hole for a 2...

Страница 8: ...ure must not exceed its maximum rating of 150 F 65 C Excessive temperatures will shorten scanner life Both requirements will be satisfied by a continuous injection of purge air at either the 3 8 housi...

Страница 9: ...FOR SPECIAL APPLICATIONS HIGH PRESSURE 35 127 HEAT INSULATING NIPPLE 35 127 HEAT INSULATING NIPPLE 60 1199 1 NPT SEALING COUPLING WITH QUARTZ WINDOW REQUIRED WHEN SCANNER LENS IS EXPOSED TO EXCESSIVE...

Страница 10: ...ot the Red wire CAUTION The Phoenix flame scanner requires 24 Vdc power for operation Connection to a 24 Vac or 120 Vac power source will damage the scanner Refer to wiring diagrams External 2 0 Amp f...

Страница 11: ...4 SCANNER CABLE COLOR CODE NEW 59 546 CABLE COLOR CODE Connector Pin No FUNCTION OLD 59 497 CABLE COLOR CODE For reference only 2 Black 24 vdc Input Black Red 6 Blue 24 vdc Input White Blue 8 Yellow...

Страница 12: ...RNAL FACTORY WIRE COLOR TB1 1 24 Volt WHITE TB1 2 24 Volt BLACK TB1 3 4 20 mA VIOLET TB1 4 4 20 mA GREY TB2 1 FAULT RELAY PINK TB2 2 FAULT RELAY RED TB2 3 FLAME RELAY WHITE RED TB2 4 FLAME RELAY WHITE...

Страница 13: ...optional Background Flame TARGET FLAME SELECT The Target Select button is used to begin the learn or store process for the target flame This will auto matically set all the necessary switching thresho...

Страница 14: ...or 4th Once you have selected the correct value Press both the Target Flame Select and Background Flame Select buttons simultaneously to store The stored value can be displayed and checked at any tim...

Страница 15: ...ns and adjusts it up to the correct level The Flame Strength should BRIEFLY GO BELOW 6 LEDs If the LEDs stay at 7 or above add orifices to minimize the signal see page 28 If the signal strength does n...

Страница 16: ...Detection Thresholds Learning Target Flame Only Step 3 Learn Store the Background Flame optional see note above Note Use Step 1 instructions on page 14 to enter the pass code before Step 3 can be carr...

Страница 17: ...test the flame relay s plus a power cycle to test the fault relay see Table 5 This test will detect 25 of possible DU failures of the device Table 5 Proof Testing Step Action 1 Bypass the safety func...

Страница 18: ...epress and release UP or DOWN button while holding Target Flame Select button All Active FLASH ON RF is energized if Target Flame Select button is held FLASH OFF Learn Target Flame completed All Activ...

Страница 19: ...rnal error SINGLE SOURCE Single flicker frequency source has been detected This is identified as not a genuine flame OVER RANGE UV IR emissions had too much energy to learn flame condition Use orifice...

Страница 20: ...6 F 80 C NEG 5 FAULT Internal voltage levels have exceeded allowed tolerances Verify supply voltage is within pub lished limits Possible fault with inter nal power supply PLUS 5 FAULT Internal voltage...

Страница 21: ...ASS CODE ACCEPTED Step 2 Commit the Default File Profile to EEPROM To save the Default Profile to the scanner s permanent memory and exit this mode Press and hold the Background Flame Select button fo...

Страница 22: ...th the Target Flame Select and Background Flame Select buttons simultaneously Use the UP or DOWN buttons to select LED number 2 passcode Press both the Target Flame Select and Background Flame Select...

Страница 23: ...een the lit LED and the scanner parameters When the Target Flame Select button is released the display will change and show a series of LEDs that corresponds to the value of the parameter selected To...

Страница 24: ...age and Binary Value Tables LED Parameter LEDs Display As Value Calculation Interpretation 8 Single Source Detected ON or OFF ON Single Source Detected OFF No Single Source 7 Peak Frequency Binary Val...

Страница 25: ...onding binary value Peak Frequency Binary Value and add them together 3 Multiply this sum times 2 5Hz for the Peak Frequency Determining Single Source Single Source Detected determination is simple If...

Страница 26: ...FF event 25 5 to 80 5 5 10 Power Spectrum Density The Power Spectrum Density setting is a percentage of the learned flame s power spectrum density The percentage is used to calculate the threshold of...

Страница 27: ...desired continue to the next parameter using the UP or DOWN buttons and program the parameter as previously discussed Step 4 Saving or Discarding Parameter Settings To SAVE the modified parameters to...

Страница 28: ...y Heat Insulating Nipple The heat insulating nipple P N 35 127 3 BSP or 35 127 1 NPT prevents heat transfer from the hot sight pipe to the scanner head Sealing Coupling with Quartz Window The sealing...

Страница 29: ...12C 53 121 4 Orifice 093 Diameter 12D 53 121 5 Orifice 109 Diameter 12E 53 121 6 Orifice 125 Diameter 12F 53 121 7 Orifice 187 Diameter 12G 53 121 8 Orifice 250 Diameter 12H 53 121 9 Orifice 375 Diame...

Страница 30: ...efective in material or workmanship or which otherwise fails to conform to the descrip tion of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MA...

Отзывы: