25
®
How to Calculate a Parameter's Value using % Values:
The method sums the percentage associated with each LED to determine parameter's value.
1. View the LED display to determine which LEDs are lit.
2. Using Table 7, for each lit LED take the corresponding percentage (Parameter % Multiplier) and add
them together.
How to Calculate Peak Frequency using the Binary Value:
The method sums binary values associated with each LED and then multiplies this sum by 2.5Hz to calcu-
late peak frequency.
1. View the LED display to determine which LEDs are lit.
2. Using Table 7, for each lit LED take the corresponding binary value (Peak Frequency Binary Value)
and add them together.
3. Multiply this sum times 2.5Hz for the Peak Frequency.
Determining Single Source:
Single Source Detected determination is simple. If no LED is lit, a single source has not been detected. If
LED 1 is lit, a single source has been detected. The two LED configurations are shown in Table 7.
Step 5 - Resetting the Trip Register and Exiting the Trip Diagnosis Mode
To
reset
the Trip Register and
exit
this mode, hold the
Background Flame Select
button for at least 2
seconds.
To
exit
this mode
without
resetting the Trip Register press both the
Target Flame Select
and
Back-
ground Flame Select
buttons.
NOTE:
Once filled, the Trip Register MUST be reset in order to store subsequent trips. It will NOT auto-
matically reset or roll-over.