Step 3 – Trip event diagnosis

Once the appropriate trip event location in the Trip Register has been selected, the LEDs will display the
reason for the trip. Use Table 5 to determine the trip code from the LED display. Multiple criteria can
cause a trip at the same instance, so multiple reasons may be set for a single trip. For example LED 1 will
be lit on a "Power Spectrum Density" trip and LED 3 will be lit for an "Average Amplitude" trip. If both
LED 1 and LED 3 are lit, the scanner tripped on both "Power Spectrum Density" and "Average Ampli-
tude"..

Table 6:

 

Trip Codes.

If additional trip events are to be viewed, use the 

UP

 or 

DOWN

 buttons to cycle to the appropriate

LED corresponding to the desired trip and then use Table 5 to determine the reason for the trip.

 

Step 4 – Viewing Parameter Values at Time of Trip

To view the scanner parameter values at the time of the trip, follow Step 2 to select the specific trip event. 

Next, press the 

Target Flame Select

 button to scroll up through the LEDs until the corresponding 

parameter LED is selected. Table 6 gives the relationship between the lit LED and the scanner 
parameters.

When the 

Target Flame Select

 button is released the display will change and show a series of LEDs that 

corresponds to the value of the parameter selected.

To select a different scanner parameter, press the 

Target Flame Select

 button and continue scrolling up 

to the parameter's LED. To return to the first scanner parameter, press the 

Background Flame Select

 

button which will redisplay the currently selected trip event and error code, then press the Target Flame 
Select button as needed. 

NOTE: Holding down the Background Flame Select button for more than two 

seconds will reset the Trip Registers and exit the diagnosis mode

LED

SCANNER TRIP  CODES

LED

SCANNER TRIP CODES

POWER SPECTRUM 
DENSITY

The power spectrum 
density has fallen below 
the applicable threshold 
value.

BEST FIT
The frequency curve of the flame no 
longer matches that of the learned 
flame.

AVERAGE AMPLITUDE

The average amplitude 
has fallen below the 
applicable threshold 
value.

SINGLE SOURCE

A single flicker frequency source has 
been detected. This is identified as 
not a genuine flame.

INTERNAL FAULT

An internal diagnostic 
detected a fault.

SIMULTANEOUS ERROR EXAMPLE

A best fit error and a power spectrum 
density error were detected at the 
same time.

LED ON

LED OFF

Содержание 85IRF series

Страница 1: ...K3 Flame Scanners are derivatives of the standard Phoenix product but utilizing an advanced optical filter This filter adjusts the optical sensitivity of the detection cell to pick up wavelengths of l...

Страница 2: ...UNTING FLANGE P N 35 318 1 2 ORDERED SEPARATELY DIMENSIONS IN INCHES MM PURGE AIR CONNECTION 3 8 18 NPT OR 3 8 19 BSP PL 1 11 1 2 NPT OR 1 11 BSP PL SIGHT PIPE CONNECTION 1 46 36 97 1 84 46 79 HOUSING...

Страница 3: ...X X 85IRF1 2QD X X X X X X X X X X X 85UVF1 2QD X X X X X X X X X X X 85UVF1 1QDK3 X X X X X X X X X X 85UVF1 2QDK3 X X X X X X X X X X X CERTIFICATION IN HAND Table 2 PART NUMBER DESCRIPTION NOTES 35...

Страница 4: ...NUMBER DESCRIPTION LENGTH METERS FEET 59 546 3 8 Conductor 3 meter cable assembly with 8 pin female connector 3 meters 9 feet 10 inches 59 546 6 8 Conductor 6 meter cable assembly with 8 pin female c...

Страница 5: ...and or use with dirty dusty fuels may require up to 15 SCFM 425 l min Pressure Adequate to overcome furnace or windbox pressure ELECTRICAL Input Power 24 Vdc nominal 20 15 supply current 200 mA Elect...

Страница 6: ...me reliably thus prohibiting the delivery of fuel to the burner Note Ensure the correct FFRT Flame Failure Response TIme is selected prior to commissioning INSTALLATION PROCEDURE 1 The best results ar...

Страница 7: ...and close to the periphery of the throat where the ultraviolet radiation is at a maximum See Figures 3 and 4 Having determined an appropriate location for the sight tube cut a clearance hole for a 2...

Страница 8: ...ure must not exceed its maximum rating of 150 F 65 C Excessive temperatures will shorten scanner life Both requirements will be satisfied by a continuous injection of purge air at either the 3 8 housi...

Страница 9: ...FOR SPECIAL APPLICATIONS HIGH PRESSURE 35 127 HEAT INSULATING NIPPLE 35 127 HEAT INSULATING NIPPLE 60 1199 1 NPT SEALING COUPLING WITH QUARTZ WINDOW REQUIRED WHEN SCANNER LENS IS EXPOSED TO EXCESSIVE...

Страница 10: ...ot the Red wire CAUTION The Phoenix flame scanner requires 24 Vdc power for operation Connection to a 24 Vac or 120 Vac power source will damage the scanner Refer to wiring diagrams External 2 0 Amp f...

Страница 11: ...4 SCANNER CABLE COLOR CODE NEW 59 546 CABLE COLOR CODE Connector Pin No FUNCTION OLD 59 497 CABLE COLOR CODE For reference only 2 Black 24 vdc Input Black Red 6 Blue 24 vdc Input White Blue 8 Yellow...

Страница 12: ...RNAL FACTORY WIRE COLOR TB1 1 24 Volt WHITE TB1 2 24 Volt BLACK TB1 3 4 20 mA VIOLET TB1 4 4 20 mA GREY TB2 1 FAULT RELAY PINK TB2 2 FAULT RELAY RED TB2 3 FLAME RELAY WHITE RED TB2 4 FLAME RELAY WHITE...

Страница 13: ...optional Background Flame TARGET FLAME SELECT The Target Select button is used to begin the learn or store process for the target flame This will auto matically set all the necessary switching thresho...

Страница 14: ...or 4th Once you have selected the correct value Press both the Target Flame Select and Background Flame Select buttons simultaneously to store The stored value can be displayed and checked at any tim...

Страница 15: ...ns and adjusts it up to the correct level The Flame Strength should BRIEFLY GO BELOW 6 LEDs If the LEDs stay at 7 or above add orifices to minimize the signal see page 28 If the signal strength does n...

Страница 16: ...Detection Thresholds Learning Target Flame Only Step 3 Learn Store the Background Flame optional see note above Note Use Step 1 instructions on page 14 to enter the pass code before Step 3 can be carr...

Страница 17: ...test the flame relay s plus a power cycle to test the fault relay see Table 5 This test will detect 25 of possible DU failures of the device Table 5 Proof Testing Step Action 1 Bypass the safety func...

Страница 18: ...epress and release UP or DOWN button while holding Target Flame Select button All Active FLASH ON RF is energized if Target Flame Select button is held FLASH OFF Learn Target Flame completed All Activ...

Страница 19: ...rnal error SINGLE SOURCE Single flicker frequency source has been detected This is identified as not a genuine flame OVER RANGE UV IR emissions had too much energy to learn flame condition Use orifice...

Страница 20: ...6 F 80 C NEG 5 FAULT Internal voltage levels have exceeded allowed tolerances Verify supply voltage is within pub lished limits Possible fault with inter nal power supply PLUS 5 FAULT Internal voltage...

Страница 21: ...ASS CODE ACCEPTED Step 2 Commit the Default File Profile to EEPROM To save the Default Profile to the scanner s permanent memory and exit this mode Press and hold the Background Flame Select button fo...

Страница 22: ...th the Target Flame Select and Background Flame Select buttons simultaneously Use the UP or DOWN buttons to select LED number 2 passcode Press both the Target Flame Select and Background Flame Select...

Страница 23: ...een the lit LED and the scanner parameters When the Target Flame Select button is released the display will change and show a series of LEDs that corresponds to the value of the parameter selected To...

Страница 24: ...age and Binary Value Tables LED Parameter LEDs Display As Value Calculation Interpretation 8 Single Source Detected ON or OFF ON Single Source Detected OFF No Single Source 7 Peak Frequency Binary Val...

Страница 25: ...onding binary value Peak Frequency Binary Value and add them together 3 Multiply this sum times 2 5Hz for the Peak Frequency Determining Single Source Single Source Detected determination is simple If...

Страница 26: ...FF event 25 5 to 80 5 5 10 Power Spectrum Density The Power Spectrum Density setting is a percentage of the learned flame s power spectrum density The percentage is used to calculate the threshold of...

Страница 27: ...desired continue to the next parameter using the UP or DOWN buttons and program the parameter as previously discussed Step 4 Saving or Discarding Parameter Settings To SAVE the modified parameters to...

Страница 28: ...y Heat Insulating Nipple The heat insulating nipple P N 35 127 3 BSP or 35 127 1 NPT prevents heat transfer from the hot sight pipe to the scanner head Sealing Coupling with Quartz Window The sealing...

Страница 29: ...12C 53 121 4 Orifice 093 Diameter 12D 53 121 5 Orifice 109 Diameter 12E 53 121 6 Orifice 125 Diameter 12F 53 121 7 Orifice 187 Diameter 12G 53 121 8 Orifice 250 Diameter 12H 53 121 9 Orifice 375 Diame...

Страница 30: ...efective in material or workmanship or which otherwise fails to conform to the descrip tion of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MA...

Отзывы: