5.5
MODBUS/TCP INTERFACE
www.maxcessintl.com
DSE-45
MI 2-315 1 A
Even though the DSE-45 acts only once on the initial receipt of
a new command, after the command has completed it is
recommended that the command and all parameters be
cleared. The command word contains fields that are needed by
some commands and ignored by others. The 16-bit command
word fields are as follows:
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
CMD
LNK SPD
UNIT
JOB
VS
Field
Description
CMD
Command
LNK
Use Virtual Sensor Linking Mask supplied in Parameter2. (JOB must be 0)
SPD
Use shift speed supplied in Parameter3. (JOB must be 0).
The shift speed is specified in mm/sec or in/sec depending on the value of the UNIT
field.
UNIT
Parameter units (00=64K; 01=mm x 10; 10=inch x 1000)
This allows the shift distance, proportional band, or position to be entered directly in
the desired unit of measurement.
For example if mm is used, 123 = 12.3mm
.
JOB
Job number (0=active job; 1 to 8 = job number)
VS
Virtual sensor number 0 to 15. When LNK=1, command affects all linked sensors.
VS Number (0 to 15) (unless link specified)
Job Number (0=ActJob; 1 to 8=Job)
Shift units (00=64K; 01=mm x 10; 10=inch x 1000)
Use link parameter (only valid on ActJob)
Use supplied speed (only valid on ActJob)
Command Code