Product overview
Festo – P.BE-CPX-CMAX-SYS-EN – en 2017-09b – English
17
2.3.3
General instructions on use of the CMAX
Fundamentals for planning and execution of positioning systems with CMAX
In the CPX terminal, a maximum of 8 CMAX modules are permitted - dependent on the bus node
(
è
The maximum permitted length (total) of the used connecting cables KVI-CP-3-... of the axis string is
30 m (total length CMAX – VPWP – sensor interface or displacement encoder;
è
Attach drive backlash-free to the application and displacement encoder.
Comply with minimum load (
è
Comply with requirements for compressed air supply (
è
Take into account emergency stop processing of an axis from the start (additional pneumatic cir
cuitry
è
Always select tubing between cylinder and VPWP valve to be as short as possible. A tube length of
60 % of the cylinder stroke length is optimal (max. tube length = cylinder stroke length).
Avoid elbow connectors as much as possible. Elbow connectors reduce the flow by up to 30 %. This
reduces the possible top speed and maximum acceleration.
Take into account power requirements of the components used. For example, the max. current con
sumption of the valve VPWP is up to 1.35 A (valve drive 1.2 A, logic 0.15 A) - without current con
sumption for the optionally usable outputs (
è
To achieve good positioning behaviour:
Feed compressed air at the cylinder on both sides.
Comply with stroke reduction in accordance with the catalogue specifications.
Stroke reduction is 10 ... 35 mm per side – dependent on the cylinder (
è
www.festo.com/catalogue).
Tip: The best positioning behaviour is achieved when only 80 % of the cylinder stroke is used and 10 %
remains on each side as reserve.
The CMAX is not suitable for:
–
cylinder lengths > 2000 mm
–
cylinder lengths > 50 mm
–
repetition accuracy < ±0.2 mm
–
speeds < 30 mm/s
–
positioning strokes < 10 mm
–
force values that lie underneath the friction of the system
2.3.4
CMAX in the CPX terminal
The CMAX is integrated into a CPX terminal as a CPX module and is controlled by the CPX bus node or
control block via the internal bus using 8-byte module output data and 8-byte module input data.
Information on control and parameterisation of the CMAX over the CPX node
è
Communication profile description, P.BE-CPX-CMAX-CONTROL-... .