CPX error group 105
(CPX-MMI: [System error B] )
No.
Reset type
Error level
Message
53
Load voltage overload on the controller
F2
F
Cause
Short circuit in the cables of the axis string (between controller and valve or valve
and sensor interface).
Measure
Check cables and modules on the axis string (e.g. wire break); replace
defective cables.
Cause
Overload on valve outputs.
Measure
Check and correct the circuitry for the outputs.
Cause
Defect in the valve.
Measure
Check cables and valve systematically; replace defective components.
Cause
Defect in CMAX.
Measure
Check CMAX and exchange if defective.
54
Operating voltage overload on the controller
F2
F
Cause
Short circuit in the cables of the axis string (between controller and valve or valve
and sensor interface).
Measure
Check cables and modules on the axis string (e.g. wire break); replace
defective cables.
Cause
Defect in the CMAX controller
Measure
Check CMAX; replace if defective.
Cause
Defect in the valve
Measure
Check cables and valve systematically; replace defective components.
Cause
Defect in displacement encoder or sensor interface
Measure
Check cables and displacement encoder or sensor interface systematically.
Replace defective components.
56
Supply pressure too low for homing
F1
R
Cause
Insufficient working pressure was detected during homing.
Measure
Check and correct operating pressure.
Check parameterisation of the operating pressure.
57
Time-out diagnostic interface: FCT device control was deactivated
W
R
Cause
Connection between PC and CPX node interrupted.
Measure
Check cables.
Cause
Communication breakdown due to FCT
Measure
Restore connection.