5-19
y codes: Link Functions
Code
Name
Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
y01 RS-485
Communication
1
–
(Station address) 1 to 255
1
–
N
Y
1
y02
0: Immediately trip with alarm
er8
–
–
Y
Y
0
(Communications error
processing) 1: Trip with alarm
er8
after running for the
period specified by timer y03
2: Retry during the period specified by timer
y03. If the retry fails, trip with alarm
er8
.
If it succeeds, continue to run.
3: Continue to run
y03 (Timer)
0.0
to
60.0
0.1
s
Y
Y
2.0
y04
(Baud rate) 0: 2400 bps
–
–
Y
Y
3
1:
4800
bps
2:
9600
bps
3:
19200
bps
4:
38400
bps
y05
(Data length) 0: 8 bits
–
–
Y
Y
0
1:
7
bits
y06
(Parity check) 0: None (2 stop bits for Modbus RTU)
–
–
Y
Y
0
1: Even parity (1 stop bit for Modbus RTU)
2: Odd parity (1 stop bit for Modbus RTU)
3: None (1 stop bit for Modbus RTU)
y07
(Stop bits) 0: 2 bits
–
–
Y
Y
0
1:
1
bit
y08 0:
No
detection 1
s
Y
Y
0
(No-response error
detection time) 1 to 60
y09
(Response interval) 0.00 to 1.00
0.01
s
Y
Y
0.01
y10
(Protocol selection) 0: Modbus RTU protocol
–
–
Y
Y
1
1: SX protocol (FRENIC Loader protocol)
2: Fuji general-purpose inverter protocol
y97
Communication Data
Storage Selection *1
0: Save into nonvolatile storage (Rewritable
times limited)
1: Write into temporary storage (Rewritable
times unlimited)
2: Save all data from temporary storage to
nonvolatile one (After saving data, the
y97 data automatically reverts to "1.")
– –
Y Y 0
y99
Loader Link Function
–
–
Y
N
0
(Mode
selection)
Frequency command Run command
0: Follow H30 data
Follow H30 data
1: Via RS-485 link
Follow H30 data
(Loader)
2: Follow H30 data
Via RS-485 link
(Loader)
(Loader)
3: Via RS-485 link
Via RS-485 link
(Loader)
(Loader)
*1 Available in the ROM version 0500 or later.