![FE FRENIC-Mini Скачать руководство пользователя страница 92](http://html.mh-extra.com/html/fe/frenic-mini/frenic-mini_instruction-manual_547580092.webp)
5-15
(H codes continued)
Code Name
Data
setting
range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
H89 Electronic Thermal
Overload Protection for
Motor
(Data retention)
0: Disable
1: Enable
–
–
Y Y 1 –
H91 PID Feedback Wire
Break Detection
(Terminal [C1])
0.0: Disable alarm detection
0.1 to 60.0: After the specified time, cause
alarm
0.1
s
Y Y 0.0
H92 Continuity of
(P)
Running *1
0.000 to 10.000 times; 999
0.001
times
Y
Y1
Y2
999
H93 (I)
0.010 to 10.000 s; 999
0.001
s
Y
Y1
Y2
999
H94 Cumulative Run Time of
Motor 1
0 to 9999 (in units of 10 hours)
–
–
N N –
5-76
H95 DC
Braking
0: Slow
–
–
Y Y
5-37
(Braking response
mode)
1: Quick
0
H96 Data
STOP
key
priority
Start
check
function
–
–
Y Y
–
STOP Key Priority/Start
Check Function
0: Disable
Disable
ACE:0
U:3
1: Enable
Disable
2: Disable
Enable
3: Enable
Enable
H97 Clear Alarm Data
0: Disable
1: Clear alarm data
–
–
Y N 0
5-74
H98 Protection/Maintenance
Function
Bit 0: Lower the carrier frequency
automatically (0: Disable; 1: Enable)
–
–
Y Y
5-76
(Mode
selection)
Bit 1: Detect input phase loss
(0: Disable; 1: Enable)
Bit 2: Detect output phase loss
(0: Disable; 1: Enable)
Bit 3: Select life judgment threshold of DC
link bus capacitor
(0: Factory default level;
1: User setup level)
Bit 4: Judge the life of DC link bus capacitor
(0: Disable; 1: Enable)
19
(Note) Alphabets in the Default setting field denote shipping destination: A (Asia), C (China), E (Europe), and U (USA).