5-3
Code Name
Data
setting
range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
F02 Operation
Method
0: RUN/STOP keys on keypad (Motor
rotational direction specified by terminal
command
FWD
/
REV
)
– –
N Y 2
1:
Terminal
command
FWD
or
REV
2: RUN/STOP keys on keypad (forward)
3: RUN/STOP keys on keypad (reverse)
5-22
F03
Maximum Frequency 1
25.0 to 400.0
0.1
Hz
N
Y
ACU:60.0
E:50.0
5-23
F04
Base Frequency 1
25.0 to 400.0
0.1
Hz
N
Y
AU:60.0
CE:50.0
F05
Rated Voltage at Base
Frequency 1
0: Output a voltage in proportion to input
voltage
1 V
N Y2
ACE:0
U: 230/
460
80 to 240: Output an AVR-controlled
voltage (for 200 V class series)
160 to 500: Output an AVR-controlled
voltage (for 400 V class series)
F06
Maximum Output
Voltage 1
80 to 240: Output an AVR-controlled
voltage (for 200 V class series)
160 to 500: Output an AVR-controlled
voltage (for 400 V class series)
1 V
N Y2
A: 220/
380
C: 200/
380
E: 230/
400
U: 230/
460
F07
Acceleration Time 1
0.00 to 3600
0.01
s
Y
Y
6.00
Note: Entering 0.00 cancels the acceleration
time, requiring external soft-start.
F08
Deceleration Time 1
0.00 to 3600
0.01
s
Y
Y
6.00
Note: Entering 0.00 cancels the deceleration
time, requiring external soft-start.
5-25
F09
Torque Boost 1
0.0 to 20.0
(percentage with respect to "F05: Rated
Voltage at Base Frequency 1")
Note: This setting takes effect when F37 = 0,
1, 3, or 4.
0.1
%
Y Y
ACE:
See
Table
A.
U:0.0
5-26
F10
1: For a general-purpose motor and Fuji
standard permanent magnet
synchronous motor with shaft-driven
cooling fan
– –
Y Y 1 5-28
Electronic Thermal
Overload Protection for
Motor 1
(Motor characteristics)
2: For an inverter-driven motor with
separately powered cooling fan
F11
(Overload detection
level)
0.00: Disable, 0.01 to 100.0
1 to 135% of the rated current (allowable
continuous drive current) of the motor
0.01
A
Y
Y1
Y2
See
Table
A.
F12
(Thermal time constant) 0.5 to 75.0
0.1
min
Y
Y
5.0
F14
– –
Y Y AC:1
EU:0
5-31
0: Disable restart (Trip immediately)
1: Disable restart (Trip after a recovery from
power failure)
2: Trip after decelerate-to-stop *1
Restart Mode after
Momentary Power
Failure
(Mode selection)
4: Enable restart (Restart at the frequency
at which the power failure occurred, for
general loads)
5: Enable restart (Restart at the starting
frequency)
F15
Frequency Limiter (High) 0.0 to 400.0
0.1
Hz
Y
Y
70.0
5-35
F16 (Low)
0.0
to
400.0
0.1
Hz
Y
Y
0.0
(Note) Alphabets in the Default setting field denote shipping destination: A (Asia), C (China), E (Europe), and U (USA).
*1 Available in the ROM version 0500 or later.