3-25
Table 3.15 Maintenance Display Items (Continued)
LED Monitor
shows:
Contents Description
5_10
Input watt-hour
data
Shows the value expressed by "input watt-hour (kWh) × E51 (whose
data range is 0.000 to 9,999)."
Unit: None.
(Display range: 0.001 to 9999. The count cannot exceed 9999. It will
be fixed at 9,999 once the calculated value exceeds 9999.)
Depending on the value of integrated input watt-hour data, the
decimal point on the LED monitor shifts to show it within the LED
monitors’ resolution.
To reset the integrated input watt-hour data, set function code E51 to
"0.000."
5_11
No. of RS-485
errors
Shows the total number of errors that have occurred in RS-485
communication after the power is turned ON.
Once the count exceeds 9.999, it will be reset to "0."
5_12
RS-485 error
contents
Shows the latest error that has occurred in RS-485 communication in
decimal format.
For error contents, refer to the RS-485 Communication User's Manual
(MEH448).
5_14
Inverter's ROM
version
Shows the inverter's ROM version as a 4-digit code.
5_16
Keypad's ROM
version
Shows the keypad's ROM version as a 4-digit code. (Available only
when an optional remote keypad is connected.)
5_23
Cumulative run
time of motor
Shows the content of the cumulative run time of the motor.
The display method is the same as for "Cumulative run time" (
5_00
)
.
5_31
Remaining time
before the next
motor 1 main-
tenance
Shows the time remaining before the next maintenance, which is
estimated by subtracting the cumulative run time of motor 1 from the
maintenance interval specified by H78. (This function applies to motor
1 only.)
Display range: 0 to 9999 The x10 LED turns ON.
Time remaining before the next maintenance (hour) =
Displayed value
×
10
Available in the ROM version 0500 or later.
5_35
Remaining
startup times
before the next
maintenance
Shows the startup times remaining before the next maintenance,
which is estimated by subtracting the number of startups from the
preset startup count for maintenance specified by H79. (This function
applies to motor 1 only.)
The display method is the same as for
5_08
above.
Available in the ROM version 0500 or later.