8-5
Item Explanation
Keypad operation using the
and
keys (with data protection
function)
Also can be set with function code (only via communication) and be
copied.
*2
Built-in potentiometer
Analog input: 0 to
±
10 V DC / 0 to 100% (terminal [12]),
4 to 20 mA / 0 to 100%, 0 to 20 mA / 0 to 100%
(terminal [C1])
Multistep frequency:
Selectable from 16 different frequencies (step 0 to 15)
UP/DOWN operation:
Frequency can be increased or decreased while the digital input
signal is ON.
Link operation:
Frequency can be specified through RS-485 communications link.
Frequency setting switching:
Two types of frequency settings can be switched with an external
signal (digital input). Switchable to frequency settings given through
the communications link or multistep frequency setting.
Auxiliary frequency setting:
Each of inputs from the built-in potentiometer and terminal [12]/[C1]
can be added to the main setting as auxiliary frequency settings.
Frequency setting
Inverse operation:
Switchable from "0 to +10 VDC/0 to 100%" to "+10 to 0 VDC/0 to
100%" by external signals.
Switchable from "4 to 20 mA DC (0 to 20 mA DC)/0 to 100%" to "20
to 4 mA DC (20 to 0 mA DC)/0 to 100%" by external signals.
Acceleration/
deceleration time
• Setting range: 0.00 to 3600 s, variable
• The two types of acceleration/deceleration time settings can be
made or selected individually (switchable during running).
• Acceleration/deceleration pattern: Acceleration and deceleration
pattern can be selected from 4 types: Linear, S-curve (weak), S-
curve (strong), and Curvilinear (maximum
acceleration/deceleration capacity of constant output).
• Shutoff of a run command causes the motor to coast to a stop.
• The acceleration/deceleration time for jogging can be set. (Setting
range: 0.00 to 3600 s)
Control
Various functions
Frequency limiter (peak and bottom limiters), Bias frequency, Gain
for frequency command, Jump frequency control, Jogging operation
*1
, Timer operation, Restart after momentary power failure
*1
, Slip
compensation
*1
, Deceleration characteristics (Forced brake
control), Current limit (Hardware current limiter)
*1
, PID control,
Automatic deceleration, Overload prevention control, Auto energy
saving operation
*1
, Cooling fan ON/OFF control, Offline tuning
*1
,
Rotation direction limitation, and 2nd motor settings
*1 Available only for induction motor drive.