5-14
(H codes continued)
Code Name
Data
setting
range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
H50
Non-linear V/f Pattern 1
(Frequency)
0.0 (Cancel), 0.1 to 400.0
0.1
Hz
N
Y
0.0
5-23
H51
(Voltage) 0 to 240: Output an AVR-controlled voltage
(for 200 V class series)
1 V
N Y2
ACE:0
U: 230/
460
0 to 500: Output an AVR-controlled voltage
(for 400 V class series)
H52
Non-linear V/f Pattern 2
(Frequency)
0.0 (Cancel), 0.1 to 400.0
0.1
Hz
N
Y
0.0
H53
(Voltage) 0 to 240: Output an AVR-controlled voltage
(for 200 V class series)
1 V
N Y2 0
0 to 500: Output an AVR-controlled voltage
(for 400 V class series)
H54 ACC/DEC
Time
(Jogging operation)
0.00 to 3600
0.01
s
Y
Y
6.00
–
H61
UP
/
DOWN
Control
0: 0.00
–
–
N Y 1
(Initial frequency setting) 1: Last
UP
/
DOWN
command value on
releasing a run command
H63 Low
Limiter
(Mode selection)
0: Limit by F16 (Frequency limiter: Low)
and continue to run
–
–
Y Y 0
1: If the output frequency lowers below the
one limited by F16 (Frequency limiter:
Low), decelerate to stop the motor.
5-35
H64 (Lower
limiting
frequency)
0.0 (Depends on F16 (Frequency limiter:
Low))
0.1 to 60.0
0.1
Hz
Y Y
2.0
–
H69 Automatic
Deceleration
(Anti-regenerative
control)
0: Disable
1: Enable (Lengthen the deceleration time
to three times the specified time under
voltage limiting control.) (Compatible with
the original FRENIC-Mini series
FRN
C1
-
)
–
–
Y Y 0
5-74
(Mode selection) 2: Enable (Torque limit control: Cancel the
anti-regenerative control if the actual
deceleration time exceeds three times
the specified one.)
4: Enable (Torque limit control: Disable
force-to-stop processing.)
H70 Overload
Prevention
Control
0.00: Follow deceleration time specified by
F08/E11
0.01 to 100.0, 999 (Cancel)
0.01 Hz/s
Y Y
999
5-75
H71 Deceleration
Characteristics
0: Disable
1: Enable
–
–
Y Y 0
H76
Automatic Deceleration
(Frequency increment
limit for braking)
0.0 to 400.0
0.1
Hz
Y
Y
5.0
5-74
H78
Maintenance Interval *1
0: Disable,
1 to 9999 (in units of 10 hours)
1 –
Y N 8760 –
H79
Preset Startup Count for
Maintenance *1
0000: Disable,
0001 to FFFF (hex.)
1 –
Y N 0000
H80 Output
Current
Fluctuation Damping
Gain for Motor 1
0.00 to 0.40
0.01
–
Y Y
0.20
(Note) Alphabets in the Default setting field denote shipping destination: A (Asia), C (China), E (Europe), and U (USA).
*1 Available in the ROM version 0500 or later.