![FE FRENIC-Mini Скачать руководство пользователя страница 133](http://html.mh-extra.com/html/fe/frenic-mini/frenic-mini_instruction-manual_547580133.webp)
5-56
Switched to motor 2 --
SWM2
(Function code data = 49)
This output signal comes ON when motor 2 is selected with the
M2/M1
terminal command
assigned to a digital input terminal. For details, refer to the descriptions of E01 through E03
(Function code data = 12).
Motor overheat detected by thermistor (PTC) --
THM
(Function code data = 56)
When the thermistor is enabled (H26 = 2), this output signal comes ON if the motor
temperature rises to the protection trigger level specified by H27.
Brake signal --
BRKS
(Function code data = 57)
This signal outputs a brake control command that releases or activates the brake.
Terminal [C1] wire break --
C1OFF
(Function code data = 59)
When terminal [C1] is used for a feedback signal under PID control, this output signal comes
ON if the [C1] wire breaks, thereby enabling it to activate the protection function.
Frequency arrival detected --
FARFDT
(Function code data = 87)
The
FARFDT
, which is an ANDed signal of
FAR
and
FDT
, comes ON when both signal
conditions are met.
Alarm output (for any alarm) --
ALM
(Function code data = 99)
This output signal comes ON if any of the protective functions is activated and the inverter
enters Alarm mode.
E30
Frequency Arrival (Hysteresis width for
FAR
)
E30 specifies the detection level (hysteresis width) for
FAR
("Frequency arrival signal").
The moment the output frequency reaches the zone defined by "Reference frequency
±
Hysteresis width specified by E30," the
FAR
comes ON.
The operation timings of signals are shown in the graph below.