Basic key operation
Before checking the status of the I/O signals, set function code E52 to "2" (Full-menu mode).
(1) When the inverter is powered on, it automatically enters Running mode. In that mode, press the
key to switch to Programming mode. The function selection menu appears.
(2) With the menu displayed, use the
and
keys to select "I/O check" (
$i_o
).
(3) Press
the key to display the codes for the I/O check item list. (e.g.
4_00
)
(4) Use
the and
keys to select the desired I/O check item, then press the
key.
The corresponding I/O check data appears. For control I/O signal terminal and control circuit
terminal input under communication control, use the
and
keys to select one of the two
different display methods.
(5) Press the key to return to the I/O check item list. Press the
key again to return to the
menu.
Table 3.12 I/O Check Items
LED monitor
shows:
Contents Description
4_00
I/O signals on the control
circuit terminals
Shows the ON/OFF state of the digital I/O terminals.
Refer to "
Displaying control I/O signal terminals
"
below for details on the display contents.
4_01
I/O signals on the control
circuit terminals under
communication control
Shows the ON/OFF state for the digital I/O terminals
that received a command via RS-485 communica-
tions. Refer to "
Displaying control I/O signal ter-
minals
" and "
Displaying control I/O signal termi-
nals under communication control
" below for de-
tails of the item displayed.
4_02
Input voltage on terminal [12]
Shows the input voltage on terminal [12] in volts (V).
4_03
Input current on terminal [C1]
Shows the input current on terminal [C1] in milliam-
peres (mA).
4_04
Output voltage to analog
meters [FMA]
Shows the output voltage on terminal [FMA] in volts
(V).
Displaying control I/O signal terminals
The status of control I/O signal terminals may be displayed with ON/OFF of the LED segment or in
hexadecimal display.
Display I/O signal status with ON/OFF of the LED segment
As shown in Table 3.13 and the figure below, each of the segments "a" to "e" on LED1 lights when
the corresponding digital input terminal ([FWD], [REV], [X1], [X2], or [X3]) is short-circuited with
terminal [CM] or [PLC]*, and does not light when it is open. Segment "a" on LED3 lights when the
circuit between output terminals [Y1] and [Y1E] is closed and does not light when the circuit is open.
Segment "a" on LED4 is for terminal [30ABC]. Segment "a" on LED4 lights when the circuit between
terminals [30C] and [30A] is short-circuited (ON) and does not light when it is open.
* Terminal [CM] if the jumper switch is set for SINK; terminal [PLC] if the jumper switch is set for SOURCE.
• If all terminal input signals are OFF (open), segment "g" on all of LEDs 1 to 4 will light
("– – – –").
• Refer to Chapter 5 "FUNCTION CODES" for details.