3-27
Basic key operation
Before viewing alarm information, set function code E52 to "2" (Full-menu mode).
(1) When the inverter is powered on, it automatically enters Running mode. In that mode, press the
key to switch to Programming mode. The function selection menu appears.
(2) With the menu displayed, use the
and
keys to select "Alarm information" (
&al
).
(3) Press
the key to display the alarm list code (e.g.
!0l1
).
In the list of alarm codes, the alarm information for the last 4 alarms is saved as an alarm history.
(4) Each time the
or
key is pressed, the last 4 alarms are displayed in order from the most
recent one as
!
,
"
,
#
, and
$
.
(5) While the alarm code is displayed, press the
key to have the corresponding alarm item
number (e.g.
6_00
) and data (e.g. Output frequency) displayed alternately in intervals of ap-
proximately 1 second. You can also have the item number (e.g.
6_01
) and data (e.g. Output
current) for any other item displayed using the
and
keys.
(6) Press
the key to return to the alarm list. Press the
key again to return to the menu.
Table 3.16 Alarm Information Displayed
LED monitor
shows:
(item No.)
Contents Description
6_00
Output frequency
Output frequency before slip compensation
6_01
Output current
Present output current
6_02
Output voltage
Present output voltage
6_03
Calculated torque
Calculated motor output torque
6_04
Reference frequency
Present reference frequency
6_05
Rotational direction
This shows the running direction being output.
f
: forward;
r
: reverse;
----
: stop
6_06
Running status
This shows the running status in hexadecimal. Refer to
Dis-
playing running status
in Section 3.4.3 "Monitoring the running
status."
6_07
Cumulative run time
Shows the cumulative power-ON time of the inverter.
Unit: thousands of hours.
When the total ON-time is less than 10000 hours (display: 0.001
to 9.999), data is shown in units of one hour. When the total time
is 10000 hours or more (display: 10.00 to 65.53), it is shown in
units of 10 hours. When the total time exceeds 65535 hours, the
display will be reset to "0" and the count will start again.
6_08
No. of startups
The cumulative total number of times an inverter run command
has been issued is calculated and displayed.
1.000 indicates 1000 times. When any number ranging from
0.001 to 9.999 is displayed, the display increases by 0.001 per
startup, and when any number from 10.00 to 65.53 is displayed,
the display increases by 0.01 every 10 startups.
When the total number exceeds 65535, the counter will be reset
to "0" and start over again.
6_09
DC link bus voltage
Shows the DC link bus voltage of the inverter's main circuit.
Unit: V (volts)