5-79
Item Specifications
V/f pattern
Linear V/f pattern only.
The load selection value (F37) will be ignored.
Auto energy saving
When driving a PMSM, the high-efficiency control is always ON.
Auto-tuning
A PMSM cannot be tuned.
Instantaneous
overcurrent limiter
Not available for a PMSM.
The H12 setting will be ignored. Even if H12 = 1, an overcurrent trip occurs due
to an overcurrent incident.
Restart mode after
momentary power
failure
When the F14 data is set to either 4 or 5, the inverter restarts with pull-in by
current.
Automatic
deceleration
(anti-regenerative
control),
When H69 = 1, the automatic deceleration is performed only on inverters
compatible with the original FRENIC-Mini series (FRN
C1
-
).
When H69 = 2 or 4, no automatic deceleration is performed.
Brake signal
Not available for a PMSM.
It is always OFF.
Jogging operation
Not available for a PMSM.
DC braking
Not available for a PMSM.
Others
Be sure to consult the motor manufacturers before actual operation.
A failure could occur.